1. For established temperature range in operating rooms, NFPA 99-2012 requires ASHRAE 170-2008, Ventilation Table 7-1 to be used.
2. For operating rooms in classes B and C, the established range for temperatures is 68 to 75 degrees Fahrenheit. Class A operating/procedure rooms should have a range of 70 to 75 degrees Fahrenheit.
3. Ventilation Table 7-1 includes an exception for temperatures to be outside of established minimum ranges when required for patients’ comfort and/or medical conditions. If a provider uses this exception and follows established policy, logging the issue isn’t required.
4. If the temperature falls below the established range, verify it won’t have a negative impact on patient care or the relative humidity level or take further action.
More articles on accreditation:
2 ASCs & outpatient facilities achieving certification and accreditation — January 2018
AAAHC-accredited center to know: Lincoln Digestive Health Center
AAAHC-accredited center to know: Northwest Endoscopy Center
At the Becker’s 32nd Annual Meeting: The Business and Operations of ASCs, taking place October 29-31 in Chicago, ASC leaders, surgeons and healthcare executives will explore strategies to drive growth, enhance operational performance, navigate reimbursement challenges and prepare for the future of ambulatory surgery. Apply for complimentary registration now.